Refrigeration Gas Detection System
by TQ Environmental plc
Model number: TQ4200
Manufacturer
TQ Environmental plc
Unit 2
Silkwood Court
Wakefield
West Yorkshire
tqplc.com accounts@tqenv.com Telephone 01924 271013
Features
- Technology
- Refrigeration Equipment
- Subtechnology
- Automated Permanent Refrigerant Leak Detection Systems
- Date added to ETL
- 1 December 2007
- Detects HCFC
- Yes
- Detects HFC
- Yes
- Detects HC
- Yes
- Detects HFO
- Yes
- Detects CO₂
- Yes
- Detects other refrigerants
- Yes
- Detects NH3
- No
- Measurement sensitivity(All gases but CO2) (ppm)
- 10
- Alarm signal threshold (CO2) (parts per million, ppm)
- 1000
- Alarm signal threshold HCFCs (ppm)
- 100
- Alarm signal threshold HFCs (ppm)
- 100
- Alarm signal threshold HCs
- 5000
- Alarm signal threshold HFOs
- 100
- Measurement sensitivity (CO2) (PPM)
- 200
- Measurement accuracy (CO2) (ppm)
- 200
- Measurement accuracy (all gases but CO2) (ppm)
- 2
- Standalone system?
- Yes
- Aspirated system with control panel?
- Yes
- Can standalone system operate in conditions of between -25 to 50 degC and RH of up to 90%?
- No
- Can aspirated system operate in conditions of between -25 to 50 degC and RH of up to 90%?
- No
- Can aspirated system control panel operate in conditions of between 0 to 50 degC and RH of up to 90%?
- Yes
- Does the product have an appropriate Conformity Assessment mark?
- Yes
Uniclass codes
Code | Title |
---|---|
Ss_75_50_28_30 | Fixed gas detection and alarm systems |
Ss_75_50_28_32 | Flow sample gas detection and alarm systems |
Ss_75_50_28_71 | Refrigerant leak detection and alarm systems |