VAM-J
by Daikin Europe N.V.
Model number: VAM1000J
Manufacturer
Daikin Europe N.V.
1 The Heights
Brooklands
Weybridge
Surrey
daikineurope.com Telephone 0845 6419000
Features
- Technology
- Heat Recovery Ventilation Units
- Date added to ETL
- 1 September 2018
- Type
- Units with Plate Heat Exchangers
- Heat recovery mechanism
- Sensible heat and latent heat
- 100% nominal air flow (m³/s)
- .278
- Pressure drop (supply air side)(plate) (Pascals - Pa)
- 84.8
- Pressure drop (exhaust air side)(plate) (Pascals - Pa)
- 78.7
- Dry heat recovery efficiency (plate type) (%)
- 80
- Effectiveness (%)
- 79.6
- Internal leakage (%)
- 8
- Net Sensible Effectiveness (%)
- 68.6
- Heat exchanger design
- Cross-flow
- Has thermal efficiency been deteremined in accordance with Commission Regulation (EU) No 1253/2014 - Ecodesign requirements for ventilation units
- Yes
- Does the product incorporate fans and filters for supplied and extracted air?
- No
- Control system type
- Sensors plus embedded control system
- Is the product (including fans, filters and sensors/contols/control interface) encased in a housing?
- Yes
- Products tested to this standard:
- JIS B 8628:2003
Uniclass codes
Code | Title |
---|---|
Pr_60_60_36_62 | Plate recuperators |