Ratiotronic 6009
by Dunphy Combustion Ltd
Model number: Ratiotronic 6009
Features
- Technology
- Boiler Retrofit Equipment
- Subtechnology
- Retrofit Burner Control Systems
- Date added to ETL
- 15 December 2019
- Does product incorporate any control valve, actuator or variable speed drive?
- No
- Is the product a microprocessor based control system for an industrial or commercial, forced draught, oil and/or gas-fired burner?
- Yes
- Exhaust gas oxygen level at 100% MCR for ETL tested product? (%)
- 2.5
- Exhaust gas oxygen level at 50% MCR for ETL tested product? (%)
- 3
- Exhaust gas oxygen level at 25% MCR for ETL tested product? (%)
- 4
- Exhaust gas CO level (maximum recorded on test) (ppmv)
- 10
- Is product designed to control a precision servomotor to adjust dampers and/or control valves which are used to modulate air or fuel flow to the burners?
- Yes
- Does product control gas-fired or dual fuel burners?
- Yes
- Does product use/control a variable speed motor controller (or variable speed drive) to operate the burner's forced draught fan?
- Yes
- Does product fully close the air dampers of the burners on shutdown?
- Yes
- Does product continuously modulate output in reponse to heat demand across a minimum turndown ratio of 4:1?
- Yes
- Does product modulate output whilst adjusting the air:fuel ratio to maintain combustion efficiency scross the required turndown range?
- Yes
- Does the product have an appropriate Conformity Assessment mark, or conform with The Electromagnetic Compatibility Regulations 2016 in respect of its design, manufacturer and testing procedures?
- Yes
Uniclass codes
Code | Title |
---|---|
Pr_65_54_33_34 | Gas burner safety devices |