FREECOOL-AD
by AIRSYS (UK) LIMITED
Model number: FCA.ID.SPL.DN20F2A2.03.BRT
Manufacturer
AIRSYS (UK) LIMITED
245 Europa Boulevard, Warrington
Email air-sys.uk enquires@air-sys.uk Telephone 0845 6099 950
Features
- Technology
- Heating, Ventilation and Air Conditioning (HVAC) Equipment
- Subtechnology
- Evaporative Air Coolers
- Date added to ETL
- 1 February 2023
- Is the product a Direct or Indirect evaporative cooler?
- Direct
- Air Flow (m3/hour)
- 12797
- Electrical power input (kW)
- 1.486
- Cooling capacity (kW)
- 37.7
- Energy Efficiency Ratio (EER)
- 25.38
- Evaporative efficiency (or saturation efficiency) (%)
- 82.80
- Water consumption resulting from the water evaporation process (m3/hour)
- 0.066
- The product is tested according to
- Other standard
- Does product include a fan which directly blows the primary air stream through a water saturated medium to cool it by evaporation?
- Yes
- Is moisture added to the air stream until it is close to the point of saturation (i.e. the wet bulb depression is close to zero)?
- Yes
- Does the product's dry bulb temperature reduce while the wet bulb temperature remains constant?
- Yes
- Does the product include one or more electrically powered fans?
- Yes
- Does the product incorporate a pump to circulate water through a water-saturated medium or to spray nozzles in an air stream?
- Yes
- Does product minimise scale build up by controlling water bleed rates?
- Yes
- Does product maintain conditions compliant with ACoP L8 legionella code of practice and guidance?
- Yes
- Does the product use air to cool a water stream?
- No
- Was the EER calculated when operated at an inlet psychometric condition of 35°C dry bulb temperature, and a 21°C wet bulb temperature?
- Yes - EER was calculated at these conditions
- Was the cooling effectiveness calculated when operated at an inlet psychometric condition of 35°C dry bulb temperature, and a 21°C wet bulb temperature?
- Yes - cooling effectiveness was calculated under these conditions
- For units with an air flow up to 4 m3/s was a external resistance of 80 PA applied when calculating the EER or cooling effectiveness?
- Yes
- Is the product capable of communicating directly with a remote monitoring & control station, across a computer network or a fieldbus, or the internet?
- Yes - across a computer network or a fieldbus
- The product complies with the general principles and requirements for cybersecurity of the following
- Neither of these standards
- Does the product have an appropriate Conformity Assessment mark?
- Yes
Uniclass codes
Code | Title |
---|---|
Pr_70_65_03_27 | Evaporative cooling units |