Technology
-
Boiler Retrofit Equipment
-
Subtechnology
-
Burners With Controls
-
Date added to ETL
-
1 October 2003
-
Product category
-
Oil fired burners rated in excess of 1200 kW
-
Max Rating (kW)
-
8500
-
Min Rating (kW)
-
1250
-
Natural gas
-
No
-
Gas oil
-
No
-
Light fuel oil
-
No
-
Heavy fuel oil
-
Yes
-
LPG
-
No
-
Propane
-
No
-
Kerosene
-
No
-
Bio-diesel
-
Yes
-
Residual oil
-
Yes
-
Tallow Oil
-
No
-
Turndown ratio
-
6.8:1
-
Exhaust gas oxygen level at 100% Load (%)
-
2.2
-
Exhaust gas oxygen level at 50% Load (%)
-
2.6
-
Exhaust Gas oxygen level at 25% load (%)
-
2.9
-
Exhaust gas CO level (maximum recorded) (ppmv)
-
15
-
Is the product fitted with dampers that fully close on burner shutdown?
-
Yes
-
Is the product a forced draught burner?
-
Yes
-
Does product modulate output continuously, or in a stepwise manner across at least 3 outputs?
-
Yes
-
Is the product fitted with a burner heat input control system which is amplitude modulating or frequency modulating (by pulse firing)?
-
Yes
-
Does the product conform to the requirements of The Pressure Equipment (Safety) Regulations 2016 in respect of its design, manufacturer and testing procedures, or have an appropriate Conformity Assessment mark?
-
Yes
-
Does product use any form of mechanical linkage between the modulating fuel valve, and its air damper or air control valve, to adjust the product’s air to fuel ratio?
-
No
-
Does the product enable compliance with the minimum requirements as stated in Annex II of the Medium Combustion Plant Directive (EU) 2015/2193 as implemented in UK domestic law, without the need for flue gas recovery?"
-
No
-
Does the product incorporate a microprocessor based burner control system?
-
Yes
-
Is a precision servomotor used to control the dampers or control valves which are used to modulate air or fuel flow to the burners?
-
Yes
-
Does product use a use a variable speed motor controller (or variable speed drive) to operate its forced draught fan
-
Yes